Product details
 
产品详情
AC220V 1200W Air Conditioner 返回上一页
1200W AC220V High Intelligence Panel Air Conditioning For Outdoor Telecom Enclosure, Base Station Room
Model:TC06-120JFH/B



AC220V 1200W Air Conditioner

Model: TC06-120JFH/B

 

Foreword
The manual mainly includes TC06-120JFH/B air conditioner’s application, technical parameters, operation instruction, product installation and maintenance, etc.

 

Note:

The manual only apply to TC06-120JFH/B air conditioner. Our company reserves the right of final explanation of the content of this manual.

Any operation on this product must be performed by professional engineering and technical personnel.


Introduction
1. Introduction And Application Scope
TC06-120JFH/B Air Conditioner is a full automation temperature control product. It uses intelligent controller to control the whole system of the air conditioner. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information. The product is widely applied in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.


2. Features
(1)Strong adaptability
(2)High intelligence 
(3)High precision
(4)High reliability
(5)Low noise 
(6)Low energy consumption
(7)With 4 way switching value detection
(8)With 1 way room air conditioner control
Voltage input range: 220VAC±15% 50/60Hz
With dry contact alarm output


3. System Principle Diagram

 

4. Standard Compliance

 

5. Technical Parameters

 

 

6. Electrical Wiring Diagram

 

 

Wiring Ports:

 

L N PE : power supply port (voltage input: 220VAC±15% 50/60Hz)
F+ F- : direct ventilation output port 
AL1 AL2: general alarm output port
A+ B- SGND : RS485 communication port
N : not connected pin

 

 

7. System Control 

 

7.1 Technical Parameter
a.2×16 Chinese/English shift LCD display, user friendly; 
b.Simultaneously display temperature and humidity inside the box and communication room temperature; 
c.Temperature measurement accuracy: 0.1 °C; humidity measurement accuracy:5%;
d.Can store 180 days’ daily event record, 1 record every day;
Daily highest temperature, lowest temperature, average temperature
Daily event record;
e.Save the former day’s daily data at 0:00 every day; Can query 180 days’ daily record information;
f.RS485 communication, YD/T 1363.1-2005 standard protocol, support remote detection and control;
g.Control mode: pulse (Non dry contact air conditioner), conducting (dry contact air conditioner)
h.Real-time control air conditioner on/off
i.Power supply: AC185V~264V/50HZ;
j.Power consumption:≤5W;

k.Working environment: -30°C~70°C; <90%RH;
l.Installation method: guide rail,hanging;
m.Dimension(L*W*H):150mm×190mm×45mm

 

 

7.2 Wiring Diagram


 

 

Diagram 4: Wiring Diagram

 

 

Board Instruction:

 

The board is divided into four blocks: F1, F2, F3, F4 (F4 is on the back).

 

 

When using non-adjustable speed fans:
All the parts in F1 should not be welded;
Parts in F2 should be welded;
Resistance in F4 (RS01, RS02) should be welded; JP1, JP2 should be short circuit; JP3, JP4 should short circuit 1-2.

 

 

When using speed adjustable fans:
All the parts in F1 should be welded;
Parts in F2 should not be welded;
Parts in F4 should not be welded and should not be short circuit.

 

F3 should be considered only when connecting coil temperature. In general case, it doesn’t need to be considered and should not be welded.

Wiring Instruction:

 

1.JD1: 48V input;
2.JD2: 48V heating output;
3.JD3: fan control terminal

   Speed adjustable fan wiring method:
   1- 48V output, fan power supply;
   2- C1 internal circulation fan control; 3- F1 internal circulation fan speed;
   4- C2 external circulation fan control; 5- F2 external circulation fan speed;
   6- 0V fan power supply grounding.

 

   Non speed adjustable fan wiring method:
   1, 6 – not connected;
   2, 3  connected with internal circulation fan (2+, 3-);
   4, 5 – connected with external circulation fan (4+, 5-);

 

4.JD4:
   1, 2: hydrogen exhaust/direct ventilation control, dry contact, normal close output;
   3, 4: dry contact output, normal open, system alarm output;
    5, 6: dry contact output, normal open, cooling system alarm output.

 

5.JD5: compressor power supply: 1-L input; 2-N common; 3-L output.
6.JD6: DI input;
7.JD7: RS485 communication 
8.J1: connected with LCD12232;
9.J2: connected with button;
10.J3: connected with temperature and humidity sensor 1 (inside cabinet);
11.J4: connected with temperature sensor (ambient);
12.J5: connected with temperature and humidity sensor 2 (backup);
13.J6: connected with NTC1 ( inner coil);
14.J7: connected with NTC2 ( outer coil);
15.J8: programming port.

 