AC220V 1600W Air Conditioner 返回上一页
1600W AC220V High Reliability Industrial Air Conditioner with Compressor For Outdoor Telecom Cabinet, UPS Room
Model:TC06-160JFH/01



AC220V 1600W Air Conditioner

Model: TC06-160JFH/01

 

1. Description
The AC Air Conditioner is a full automation temperature control product. It uses intelligent controller to control the whole system of the air conditioner. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information. The product is widely applied in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.

 

2.Features

(1)Strong adaptability
(2)High intelligence 
(3)High precision
(4)High reliability
(5)Low noise 
(6)Low energy consumption
(7)With 4 way switching value detection
(8)With 1 way room air conditioner control
(9) Voltage input range: 220VAC±25% 50/60Hz
(10) With dry contact alarm output 

3.System Principle Diagram

 

4. Standard Compliance

 

5. Technical Parameters

 

 

6. Electrical Wiring Diagram

 

Wiring Ports:

L N PE : power supply port (voltage input: 220VAC±25% 50/60Hz)
A+ B- GND : communication port
AL1 AL2: general alarm output port
F+ F- : direct ventilation output port 
N : not connected pin

 

 

7. System Control 

 

7.1 Technical Parameter

a.2×16 Chinese/English shift LCD display, user friendly; 
b.Simultaneously display temperature and humidity inside the box and communication room temperature; 
c.Temperature measurement accuracy: 0.1 °C; humidity measurement accuracy:5%;
d.Can store 180 days’ daily event record, 1 record every day;
e.Daily highest temperature, lowest temperature, average temperature
f.Daily event record;
g.Save the former day’s daily data at 0:00 every day; Can query 180 days’ daily record information;
h.RS485 communication,RTU-Modbus protocol, support remote detection and control;
i.Controllable air conditioner quantity:2 sets. 1 set of air conditioner for communication room, and 1 set of small air conditioner for thermostatic box.
j.Control mode: pulse (Non dry contact air conditioner), conducting (dry contact air conditioner)
k.Real-time control air conditioner on/off
l.Power supply: AC85V~265V/50HZ;
m.Power consumption:≤5W;
n.Working environment: -30°C~70°C;<90%RH;
o.Installation method: guide rail,hanging;
p.Dimension(L*W*H):150mm×190mm×45mm

 

 

7.2 Wiring Diagram

 

Diagram 4: Wiring Diagram

 

脚注信息

 