Heat Exchanger
1. Application
ET9090210 Integrated Outdoor Telecom Cabinet is mainly used in wireless communication base station, such as 3G, 4G system, communication/network integrated service, access/transmission switching station, emergency communication/transmission, etc.
2. Features
(1) The cabinet is dustproof, sunproof and rainproof, which is used in outdoor environment.
(2) Cabinet cooling: fans and heat exchanger. (Other cooling option: air conditioner). MTBF≥50000h
(3) The layout of the cabinet is reasonable, which will facilitate cable access, fixing and grounding. There are entrance holes individually for power cable, signal cable and optical cable.
(4) All the cables used in the cabinet are made from flame retardant materials.
3. Technical Parameters
Item |
Type |
Technical Parameter |
Structure |
Dimension |
External Dimension: H*W*D 2100*900*900mm Internal Dimension: H*W*D 1800*800*800mm |
Layout |
1 compartment |
|
Equipment Installation Method |
19” rack |
|
Door |
With one front door , and special lock for outdoor cabinet (support padlock) |
|
Material |
Galvanized steel ; 1.5mm thick outer plate, 0.8mm thick inner plate |
|
Heat Insulation |
There are heat insulation between inner wall and outer wall. The insulation material is 20mm PEF |
|
Structure |
Assembled |
|
Ingress Protection |
IP55 |
|
Temperature Control |
Cooling |
DC48V heat exchanger and DC48V fans |
Lightning Proof |
Grade B lightning proof |
Nominal: 60KA, Max.: 100KA |
Lighting |
LED lamp |
48V LED lamp |
Temperature |
Temperature |
Working Temperature: -40°C ~ +55°C |
|
|
Storage Temperature: -50°C ~ + 70°C |
|
|
Transport Temperature: -50°C ~ +70°C |
Humidity |
Relative Humidity |
5% ~ 100% |
Pressure |
Air Pressure |
62kpa ~ 101kpa (similar to 0m ~ 5000m altitude) |
Radiation Intensity |
Solar Radiation Intensity |
1120 ×(1±5%)W/m2 |
4. Accessories List
No. |
Item |
Quantity |
Unit |
Specs |
1 |
Outdoor Telecom Cabinet |
1 |
Set |
(1) External Dimension: H*W*D 2100*900*900mm Internal Dimension: H*W*D 1800*800*800mm; (2) One compartment: 19” standard installation rack; (3)With one front door , and special lock for outdoor cabinet (support padlock); (4) Material: galvanized steel; 1.5mm thick outer plate, 0.8mm thick inner plate. |
2 |
Heat exchanger |
1 |
Set |
Cooling capacity: 190W/K, DC48V; Model: HE06-190SEH/01(CW031). |
3 |
Auxiliary Direct Ventilation Fans |
2 |
PC |
12038 DC48V |
4 |
Environment Monitoring Unit |
1 |
Set |
1U, 19”, Model: SM2400 |
5 |
Water Sensor |
1 |
PC |
|
6 |
Smoke Sensor |
1 |
PC |
|
7 |
Temperature and Humidity Sensor |
1 |
PC |
|
8 |
Door Sensor |
2 |
PC |
One for controlling LED lamp, the other for open door alarm |
9 |
LED Lamp |
1 |
PC |
DC48V |
10 |
Power Distribution Unit |
1 |
Set |
Grade B Lightning Proof AC Input: 63A/2P *1; AC Output: 16A/1P*4; DC Output: 16A/1P*4; Input Voltage: AC220V. |
11 |
Package |
1 |
Set |
Wooden Case |